Generator Fuel Consumption Chart: Propane, Gasoline, Diesel and Natural Gas by kW and Load

A generator at a quarter load spends far more fuel per unit of electricity than the same machine at three quarters. The tool below turns a cylinder, a jerrycan or a buried tank into hours of running; the chart under it gives the hourly burn from 2 kW to 38 kW at four load points.

Loading regional defaults…

kW
ft
°F

BURN RATE

0 gal/hr

RUNTIME

0 hr

THAT IS

0 days at this load

FUEL PER kWh

0 gal/kWh

Fuel energy going in: . Usable output here after elevation and temperature derating: .

The chart

Pick a load point and a unit system; click a column heading to sort. Printing gives all four tables without the controls.

Fuel burn per hour at 50% of rated output. Sizes are the generator’s rating in kilowatts of alternating current. Dashes mark combinations that are not a normal product: gasoline stops where portables stop, diesel starts at the liquid-cooled sizes, natural gas needs a pipe.
SizeLoadGasoline
gal/hr
Diesel
gal/hr
Propane
gal/hr
Propane
lb/hr
Natural gas
cu ft/hr
2 kW1 kW0.220.321.36
3 kW1.5 kW0.320.472.01
5 kW2.5 kW0.520.763.22
7 kW3.5 kW0.701.024.3293.2
9 kW4.5 kW0.861.265.33115
12 kW6 kW1.040.741.375.79125
14 kW7 kW1.180.861.556.57142
17 kW8.5 kW1.371.031.817.65165
20 kW10 kW1.202.078.77189
22 kW11 kW1.272.249.48205
26 kW13 kW1.402.5410.8232
30 kW15 kW1.502.8712.2262
34 kW17 kW1.673.1913.5292
38 kW19 kW1.833.5014.8320

How this is calculated

One equation runs the page. Output in kilowatts times 3,412 Btu per kilowatt-hour is the energy leaving the machine each hour; divide by engine efficiency for the fuel energy going in, then by the energy in a unit of fuel.

Efficiency is the only modeled part, and it climbs with both size and load. The curve is fitted to the sheets below: 16.5 percent at full load on a 2 kW portable, 23.5 on a 22 kW standby, 28.8 on a 30 kW diesel, times 0.57 at quarter load and 0.78 at half load on a spark-ignition engine, 0.72 and 0.86 on a diesel.

Worked example, a 22 kW propane standby at half load. Eleven kilowatts out is 37,533 Btu an hour; at 18.3 percent, 204,800 Btu goes in. Propane holds 91,452 Btu per gallon and 21,591 per pound, so 2.24 gal/hr, 9.5 lb/hr, 4.3 kg/hr. A barbecue cylinder empties in two hours.

Energy contents used throughout. Gasoline 120,214 Btu/gal, diesel 137,381 and propane 91,452, from the Energy Information Administration; propane per pound, 21,591, from Quality Steel Corporation. Natural gas at the nominal 1,000 Btu per cubic foot Generac and Kohler size pipework on, against the Administration’s 1,036 for delivered gas, so real burn runs a few percent under the chart.

Read any cell as the middle of a band 20 percent either side: Generac’s 22 kW burns 3.90 gal/hr of propane flat out, Kohler’s 26RCA 3.55 while making four more kilowatts.

Quick answers

How much propane does a 22 kW generator use per hour?

Around 2.2 gal/hr at half load and 3.5 gal/hr flat out, or 9.5 and 15 pounds. Generac’s own sheet lists 2.53 and 3.90 for its 22 kW models.

How much diesel does a generator burn per hour?

Kohler’s 30REOZK sheet gives 0.9, 1.5, 2.1 and 2.6 gal/hr at quarter, half, three-quarter and full load. The 20 kW 20REOZK gives 0.6, 1.1, 1.6 and 2.1.

What load is a generator most efficient at?

On fuel alone the curve is flat from half load up. Below half it climbs steeply, and under 30 percent a diesel runs too cool to burn its fuel cleanly.

How long will a 20 lb propane cylinder run a generator?

About six hours on a 5 kW portable at half load, two hours on a 22 kW standby. The cylinder holds roughly 431,800 Btu.

Does altitude change fuel consumption?

It cuts the power the engine can make, pushing the same house load to a higher percentage of what is left. Generac quotes 3.5 percent lost per 1,000 feet, Kohler 4 percent.

What the manufacturers publish

Published fuel consumption per hour, quoted from the manufacturers’ own sheets. Sheet codes and revision dates in the sources below. Read September 2026.
MachineFuel25%50%75%100%
Kohler 26RCA, 26 kW on propanePropane64 cu ft85 cu ft111 cu ft129 cu ft
Kohler 26RCA, 24 kW on gasNatural gas137 cu ft180 cu ft238 cu ft290 cu ft
Generac Guardian, 22 kW on propanePropane2.53 gal3.90 gal
Generac Guardian, 19.5 kW on gasNatural gas228 cu ft327 cu ft
Kohler 30REOZK, 23–31 kW standbyDiesel0.9 gal1.5 gal2.1 gal2.6 gal
Kohler 20REOZK, 20 kW standbyDiesel0.6 gal1.1 gal1.6 gal2.1 gal
Kohler 20ROZJ, 25–27 kW standby at 60 HzDiesel1.0 gal1.3 gal1.5 gal2.1 gal
Honda EU2200i, 1.8 kW ratedGasoline0.12 gal0.30 gal
Champion 201393, 3.8 kW ratedGasoline0.34 gal

Honda and Champion figures are published run times divided into their tanks: 0.95 gallons over 3.2 and 8.1 hours, 4.7 gallons over 14 hours at half load. Kohler’s G4-315 sheet prints its own conversion: 36.39 cubic feet of propane vapor to the gallon, 8.58 to the pound.

The cliff below half load

Plot fuel per kilowatt-hour against load and the same shape appears on every sheet: a cliff on the left, a flat plain from half load rightward. The steep part is the engine spending friction, pumping and heat losses on a load too small to dilute them.

Anywhere from half load to full costs much the same fuel per unit. The reason to stop at three quarters is the headroom a motor needs to start, so that band is where a machine should normally sit.

100125150 175200 25%50%75%100% Load, percent of the machine’s rating Fuel per kWh, indexed to each machine’s best point = 100 Kohler 26RCA, 26 kW, propane Kohler 20ROZJ, 25–27 kW, diesel Kohler 30REOZK, 23–31 kW, diesel Kohler 20REOZK, 20 kW, diesel
Indexing each machine to its own best point removes the rating, leaving only the shape. The propane machine has the deepest cliff; the 20ROZJ, on a 2001 sheet, bottoms out at 75 percent and worsens slightly at 100; the current common-rail 20REOZK is nearly flat across.

Diesel has a second reason to stay loaded. Kohler’s paper on no-load exercising (Power Systems Topics 130): run below 30 percent of capacity for extended periods and the engine cannot sustain the temperatures that burn fuel completely. The remainder builds in the exhaust as wet stacking, fouling injectors and wearing valve guides.

  • Two smaller machines alternating beat one large one loafing.
  • A battery carrying the overnight base load lets the engine run hard for a few hours instead of idling all night.

Cold weather and propane vaporization

Propane leaves a tank as vapor, so the tank has to boil the liquid. Boiling takes heat, which arrives through the wetted steel from the air outside. Cold air, or a nearly empty tank, and the vapor stops arriving at the rate the engine wants.

The engine sees falling pressure, runs lean, hunts and shuts down, while frost climbs the tank.

Vapor draw in Btu per hour with 40 percent liquid in the tank, from Quality Steel Corporation’s approximate vaporization capacities for domestic systems. The last column is that figure read back through the chart above.
Tank, water capacityAt 20 °F (−7 °C)At 60 °F (16 °C)Biggest propane set it feeds at 20 °F
120 gal (450 L)235,008417,792about 15 kW at full load
250 gal (950 L)406,080721,920about 30 kW at full load
500 gal (1,900 L)634,0321,127,168about 48 kW at full load
1,000 gal (3,800 L)1,088,4721,978,051about 83 kW at full load

A 22 kW standby at full load wants roughly 319,000 Btu an hour, so at 20 °F a 120 gallon tank cannot feed it and a 250 gallon tank can. Cylinders are weaker again, which is why a barbecue bottle frosts within minutes on anything past a camping generator.

United States vessels: 20 lb and 30 lb cylinders, 100 lb cylinders paired on a switchover regulator, 120 to 1,000 gallon tanks at 80 percent.

European vessels: 11 kg and 13 kg exchange bottles, 47 kg cylinders paired on a changeover regulator, 1,000 to 2,700 liter bulk tanks at 80 percent. Mixed bottles carry butane, which stops boiling near freezing, so a cold site wants pure propane.

Altitude, heat and the percentage

Thin air and hot air both cut engine power. Generac’s manual for its 10 to 24 kW air-cooled generators puts the loss at approximately 3.5 percent per 1,000 feet above sea level and 1 percent per 10 °F above 60 °F. The tool above uses those figures.

Kohler is harsher on the same class of machine: 4 percent per 1,000 feet above 500 feet, 2 percent per 10 °F above 60 °F, printed on the 26RCA sheet.

Hourly burn does not jump. The denominator changes. At 6,000 feet a 22 kW machine behaves like a 17.4 kW one, so a 12 kW house load that sat at 55 percent of rating now sits at 69, and the starting headroom the well pump needed has gone.

On 120 V and 240 V split-phase the derated figure is what the house load has to fit inside, motor surge on top. Work it through with the backup power calculator.

On 230 V single phase or 400 V three phase the derated figure is what the house load has to fit inside, and three phase must sit balanced across the phases. Work it through with the backup power calculator.

Turning a tank into days

Energy in the vessel divided by energy per hour gives hours, which is all the tool at the top does. Four hours morning and evening with a battery covering the gaps stretches a 500 gallon tank from seven and a half days to more than three weeks.

Usable energy per vessel, at the energy contents listed above. Propane tanks filled to 80 percent; jerrycans, cylinders and diesel subbase tanks at their marked capacity.
VesselFuelUsable energy, Btu
20 lb cylinder (9 kg)Propane431,800
11 kg bottlePropane523,600
100 lb cylinder (45 kg)Propane2,159,100
120 gal tank at 80%Propane8,779,000
500 gal tank at 80%Propane36,581,000
1,000 L tank at 80%Propane19,326,000
5 gal jerrycanGasoline601,100
20 L jerrycanDiesel725,800
100 gal subbase tankDiesel13,738,000

Where this chart stops

It is a planning chart, not a meter. Fuel quality, engine hours, governor tuning and the shape of the load all move the real number, and an inverter generator that drops below 3,600 rpm beats this curve at light load. Starting, warm-up and exercise cycles burn fuel that never reaches the house.

Sources

Generac Guardian 20–24 kW specification sheet, A0000937814 Rev. F, 09/28/2022, and owner’s manual for 60 Hz air-cooled generators 10 to 24 kW, A0000973303 Rev. A, 10/09/2020. Kohler sheets G4-315 (26RCA), G5-81 (20ROZJ) 6/01c, G5-435 (20REOZK) 8/23m, G5-436 (30REOZK) 8/23. Justin Loritz, Feasibility and Benefits of No-Load Exercising, Kohler Power Systems Topics 130. Honda EU2200i specifications, 0.95 gallon tank, 3.2 to 8.1 hours. Champion 201393, 4.7 gallon tank, 14 hours at half load on gasoline. Energy Information Administration, Btu content per unit. Quality Steel Corporation vaporization capacities. All read September 2026.

Go deeper

Size the machine before costing the fuel: the backup power calculator turns a load list into kilowatts, fed by the appliance wattage chart. Then what size generator backs up a whole house, whole home generator cost and standby generator against home battery.

Gear that fits these numbers

Backup Power & Transfer

The hardware between a generator and a house that stays lit. Linked direct to the makers — take your result with you.

Reliance Controls

Pro/Tran 2 transfer switches & inlet boxes

The standard manual transfer switch — six to ten circuits, code-legal backfeed prevention.

Generac

Home standby & portable generators

The reference brand for whole-house standby; portables with electric start and CO shutoff.

Champion

Dual-fuel inverter generators

Propane-or-gas inverters that run quiet enough for a neighborhood outage.

The full Backup Power & Transfer list